INSTALLATION INSTRUCTIONS
RECOMMENDED MODELS
P/N 006355
Notice to installing contractor: Instructions must remain with installation.
SECTION: 6.10.001
FM0447
Rev. A
1009
Supersedes
0809
PREINSTALLATION CHECKLIST - ALL IN STAL LA TIONS
*Ef uent systems should specify that pumps should not handle solids exceeding three fourths inch (¾") in order to prevent large solids from entering leeching elds, mound systems etc.
(Model 49 and 70 Series have 3/8" solids capability, 50, 90, 140, 145/4145, 151, 371 and 372 Series have ½", 130 Series has 5/8", 152,153, and 160/4160/180/4180, 373 Series have
¾".) Where codes permit, sewage pumps can be used for ef uent systems. Nonautomatic pump(s) with external level control recommended for septic tank ef uent applications.
Product information presented
here re ects con di tions at time
of publication. Consult factory
re gard ing dis crep an cies or
in con sis ten cies.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
DATE INSTALLED:
MODEL NUMBER:
1. Inspect your pump. Occasionally, products are damaged during shipment. If the unit is damaged, contact your dealer before using. DO NOT remove the test plugs in the cover nor the motor housing.
2. Carefully read the literature provided to familiarize yourself with speci c details regarding in stal la tion and use. These materials should be retained for future reference.
NOTICE: VENT HOLE FOR
CHECK VALVE
SEE #3 IN CAUTION SECTION
BELOW AND #4 ON PAGE 3
EFFLUENT*/SUMP/DEWATERING SEWAGE
49, 50 Series, 70 Series, 98 Series 211 Series, 264 Series
130 Series, 140/4140, 145/4145 Series, 150 Series, 160/4160 Series 260 Series, 270/4270 Series
180/4180 Series, 191, 371, 372, 373 280/4280 Series, 290/4290 Series
SEE BELOW FOR
LIST OF CAUTIONS
SEE BELOW FOR
LIST OF WARNINGS
1. Make certain that the receptacle is within the reach of the pump’s pow er supply cord. DO NOT
USE AN EXTENSION CORD. Extension cords that are too long or too light do not deliver suf cient
voltage to the pump motor. But, more important, they could present a safety haz ard if the insulation
were to become damaged or the con nec tion end were to fall into the sump.
2. Make sure the pump electrical supply circuit is equipped with fuses or circuit breakers of
proper capacity. A separate branch circuit is rec om mended, sized ac cord ing to the “National
Elec tri cal Code” for the current shown on the pump nameplate.
3. Testing for ground. As a safety measure, each electrical outlet should be checked for ground
using an Underwriters Laboratory Listed circuit analyzer which will indicate if the power, neutral
and ground wires are correctly connected to your outlet. If they are not, call a quali ed licensed
electrician.
4. For Added Safety. Pumping and other equipment with a 3-prong grounded plug must be connected
to a 3-prong grounded receptacle. For added safety the receptacle may be protected with a ground-
fault circuit interrupter. When a pump needs to be connected in a watertight junction box, the plug
can be removed and spliced to the supply cable with proper grounding. For added safety this circuit
may be protected by a ground-fault circuit in ter rupt er. The complete in stal la tion must comply with
the National Electrical Code and all applicable local codes and ordinances.
5. FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POW ER SOURCE BE FORE
HANDLING. Single phase pumps are sup plied with a 3-prong ground ed plug to help protect you
against the possibility of electrical shock. DO NOT UNDER ANY CIRCUM STANCES RE MOVE
THE GROUND PIN. The 3-prong plug must be inserted into a mating 3-prong grounded receptacle.
If the in stal la tion does not have such a receptacle, it must be changed to the prop er type, wired
and ground ed in ac cor dance with the National Elec tri cal Code and all applicable local codes and
or di nanc es. Three phase pumps require motor starting devices with motor overload pro tec tion. See
FM0486 for duplex in stal la tions.
6. The tank is to be vented in accordance with local plumbing code. Pumps must be in stalled in ac-
cor dance with the National Electrical Code and all ap pli cable local codes and ordinances. Pumps
are not to be installed in locations clas si ed as hazardous in accordance with National Electrical
Code, ANSI/NFPA 70.
7. “Risk of electrical shock” Do not remove power supply cord and strain relief or connect conduit
directly to the pump.
8. Installation and servicing of electrical circuits and hardware should be performed by a quali ed
li censed electrician.
9. Pump installation and servicing should be performed by a quali ed person.
10. Risk of electric shock - These pumps have not been investigated for use in swimming pool and
marine areas.
11. According to the state of California (Prop 65), this product contains chemicals known to the state
of California to cause cancer and birth defects or other reproductive harm.
1. Check to be sure your power source is capable of handling the voltage re quire ments of the motor,
as indicated on the pump name plate.
2. The installation of automatic pumps with variable level oat switch es or nonautomatic pumps using
auxiliary variable level oat switches is the re spon si bil i ty of the in stall ing party and care should be
tak en that the tethered oat switch will not hang up on the pump apparatus or pit peculiarities and
is secured so that the pump will shut off. It is recommended to use rigid piping and ttings and the
pit be 18" or larger in diameter.
3. Information - vent hole purpose. It is necessary that all sub mers ible sump, ef uent, and sewage
pumps capable of handling various sizes of solid waste be of the bottom intake design to reduce
clog ging and seal failures. If a check valve is incorporated in the installation, a vent hole (approx.
3/16") must be drilled in the discharge pipe below the check valve and pit cover to purge the unit
of trapped air. Trapped air is caused by agitation and/or a dry basin. Vent hole should be checked
periodically for clogging. The 50 or 90 Series pumps have a vent lo cated in the pump housing
opposite the oat, ad ja cent to a housing lug, but an additional vent hole is recommended. The
vent hole on a High Head application may cause too much turbulence. You may not want to drill
one. If you choose not to drill a vent hole, be sure the pump case and impeller is covered with liquid
before connecting the pipe to the check valve and no inlet carries air to the pump intake. NOTE:
THE HOLE MUST ALSO BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY. Water
stream will be visible from this hole during pump run periods.
4. Pump should be checked frequently for debris and/or build up which may interfere with the oat “on”
or “off” position. Repair and service should be performed by Zoeller Pump Company Authorized
Service Station only.
5. Dewatering and ef uent sump pumps are not designed for use in pits handling raw sewage.
6. Maximum operating temperature for standard model pumps must not ex ceed 130°F (54°C). Model
49 max. temperature must not exceed 104ºF (40ºC). The 70 and 211 Series max. temperature must
not exceed 110ºF (43ºC).
7. Pump models 188/4188, 189/4189, and 295/4295 nonautomatic pump must run totally submerged
and CSA certi ed pumps must be operated submerged with “off - on” level controls.
8. Pump models 266, 267, 268, 137 and 139 must be operated in an upright position. Do not attempt
to start pump when tilted or laying on its side.
9. Do not operate a pump in an ap pli ca tion where the Total Dynamic Head is less than the minimum
Total Dynamic Head listed on the Pump Performance Curves.
10. Model 49 is for indoor use only.
REFER TO WARRANTY ON PAGE 2.
NOTE: Pumps with the “UL” mark and pumps with the “US” mark are tested to UL Standard UL778.
CSA Certi ed pumps are certi ed to CSA Standard C22.2 No. 108.
Vista de página 0
1 2 3 4

Resumo do Conteúdo

Página 1 - INSTALLATION INSTRUCTIONS

1© Copyright 2009 Zoeller Co. All rights reserved.INSTALLATION INSTRUCTIONSRECOMMENDED MODELSP/N 006355Notice to installing contractor: Instructions

Página 2 - SERVICE CHECKLIST

2© Copyright 2009 Zoeller Co. All rights reserved.in the paragraph above is in lieu of all other warranties expressed or implied; and we do not author